View fire system conditions at Building Management Network workstations?
YES, The Building Management Network connection does not impact fire alarm system operation. This
application is considered supplemental to a Simplex fire alarm system. All Simplex BACnet objects
configured from the BACpac Portal are available to be displayed at a BACnet compatible workstation
(fire alarm and trouble by point or zone; priority 2 alarm and trouble by point or zone; supervisory
service conditions; utility points on/off; etc.). The workstation must be configured by others for
this annunciation.
Provide smoke alarm status to HVAC control systems?
YES, But, the Portal is not listed for smoke control management use by any HVAC supplier at this time.
The Building Management supplier must submit the fire alarm system and interface for agency listing as a
Smoke Management System under UL category UUKL. Simplex cannot obtain listing for a third party but will
support Third party efforts to obtain UUKL listing.
Configure a network of Simplex fire alarm panels for alarm reporting?
Not Likely, A Building Management network supplier must have our fire alarm system and their network
components agency listed for the purpose. This is unlikely because of today¡¦s listing requirements to
re-submit any component changes. Computer technology changes faster than the listing process can keep
up with making this effort too costly.
Allow a Building Management network to control the fire panel functions such as
Acknowledge, Silence, Reset, Point Disable/Enable, On/Off utility control?
The Portal is not listed for this use. The system must be listed for the purpose before any control
operations to the fire alarm panels are allowed.